Specifications for Doors

Name:

Hollow Metal Doors

Descripiton:

All doors shall be 1-3/4" thick flush type. Door panels shall be nominal 20 gauge galvanized steel reinforced by lamination to a honeycomb core enclosed with 16 gauge end channel. The hinge reinforcements shall be nominal 7 gauge and the lock reinforcements shall be nominal 16 gauge. Door frames shall be 4-3/4" deep double rabbeted type of nominal 16 gauge galvanized steel.

Doors and frames shall be factory painted with one coat of baked on primer. All doors shall be preassembled in their frames and hardware installed and tested prior to shipment. Field installation of single leaf door units shall not require any frame assembly, or door hanging.

Standard:
  • 3 - 4-1/2" x 4-1/2" standard weight, plain bearing hinges per ANSI A5133 630 Satin Stainless Finish with non- rising pins.
  • 3-11/16" wide x 5/8" high extruded aluminum threshold. (Out Swing)
  • 1/4" x 1/2" silicone rubber weatherstripping.
Options:
  • 3 - 4 1/2" x 4 1/2" standard weight ball bearing hinges per ANSI A5112 630 Satin Stainless Finish with non-rising pins.
  • Mortise lockset per ANSI A156.13, Series 1000, Grade 1, Function F13, 626 Satin Chrome Finish (levers both sides).
  • Cylindrical key in knob lockset per ANSI A156.2, Series 4000, Grade 2, Function F81, 630 Satin Stainless Steel Finish.
  • Passage set per ANSI A156.2, Series 4000, Grade 2, Function F75, 626 Satin Chrome Finish.
  • Door closer is certified to conform to ANSI 156.4 Grade 1 and meets exterior barrier free codes in 689 Aluminum Lacquer Finish.
  • Rim Type "Cross Bar" panic device per ANSI A156.3, Type 1, Grade 1, Function 05, with 627 Satin Aluminum Finish.
  • Rim type "Push Pad" panic device built to ANSI A156.3, Type 1, Grade 2, Function 08 with 689 Aluminum Lacquer Interior Finish and 626 Satin Chrome Exterior Finish.
  • 23" wide X 20" high Adjustable blade louver with mesh insect screen.

 

Specifications for Framed Openings

Name:

Framed Openings for Overhead Doors

Descripiton:

Framed openings shall be constructed from nominal 12 gauge galvanized steel. The jambs and head shall provide a minimum 2-1/2" wide inside surface for field mounting of overhead door track and hardware. Head and jamb covers to be nominal 24 gauge, embossed, painted wall color.

Standard:  
Options:
  • Sliding doors shall consist of a nominal 16 gauge galvanized steel channel framing system and embossed nominal 24 gauge prepainted arctic white ribbed covering. The doors shall be top hung design with a bottom guide rail.
  • Removable wall sections shall consist of a framed opening capable of supporting roof and wall loads when the wall section is removed. The removable section shall consist of the same materials as the permanent wall. Section shall be removable by unbolting from the inside of the building.

 

Specifications for Windows

Name:

Horizontal Sliding Windows

Descripiton:

Sliding windows shall be furnished factory glazed and complete with all attaching hardware and screen. The window unit shall be factory assembled for single unit installation.

All window sash sections shall be of 6063-T5 extruded aluminum and shall be color finished in white or bronze baked enamel. Windows shall meet or exceed ANSI/AAMA 101 and AAMA 1302.5 Specifications.

Standard:
  • 1/2" insulated glass.
Options:
  • 1/4" polished wire glass.
  • 1/4" acrylic glazing.
  • 1/4" obscure glass.
  • 1/4" polycarbonate glazing.

Name:

Fixed Window

Descripiton:

Fixed windows shall be furnished factory glazed and complete with all attaching hardware. The window unit shall be factory assembled for single unit installation. All window sash sections shall be formed from nominal 18 gauge galvanized G90 steel and factory color finished white or bronze baked on enamel.

Standard:
  • 1/2" insulated glass.
Options:
  • 1/4" polished wire glass.
  • 1/4" acrylic glazing.
  • 1/4" obscure glass.
  • 1/4" polycarbonate glazing.

 

Specifications for Wall Opening Kits

Name:

Wall Opening Kit

Descripiton:

The building manufacturer shall supply all necessary framing and connectors to structurally replace the panels removed by any wall opening. All trim and flashings required to make weathertight the unit placed in any opening shall be provided by the supplier of the unit being installed.

 

Specifications for Louvers

Name:

Adjustable Wall Louvers

Descripiton:

Adjustable louvers shall be of self framing design. The louver frame shall be of nominal 14 gauge formed aluminum and the louver blades shall be nominal 12 gauge extruded aluminum. Finish shall be natural mill finish and shall not require field painting.

Blades shall be pivoted on 1/2" diameter aluminum pivot pins through nylon flanged bearings and operated by means of a pull bar operating handle. All louvers shall be complete with an exterior mounted 18 X 14 aluminum mesh insect screen.

Options:
  • Wall louvers shall have removable filters.
  • Motor Operator
  • 1/4" obscure glass.
  • 1/4" polycarbonate glazing.

Name:

Fixed Wall Louvers

Descripiton:

Fixed louvers shall be nominal 26 Gauge., G90 Galvanized Steel, 16"x16", general purpose type of self framing design with free area of 75 square inches. Finish shall be bright galvanized All louvers shall be complete with #8 insect screening.


Name:

Gable Louvers

Descripiton:

Gable Louvers shall be fixed blade type with blades set on a 45 degree slope. Blades and frames shall be nominal 14 gauge extruded aluminum with natural mill finish. Louvers shall include #18-14 aluminum mesh insect screens.

 

Specifications for Exterior Roof Accessories

Name:

Turbine Ventilator

Descripiton:

Turbine vents shall be wind driven rotary type gravity roof ventilator with 8" or 12" diameter throat, fabricated from galvanized steel, externally braced.


Name:

Circular Roof Ventilators

Descripiton:

Stationary ventilators for 3" or 4" roofs shall be 12" diameter gravity type fabricated from aluminum and shall be furnished complete with bird screen, operable disc type damper with chain and base.


Name:

Power Roof Ventilators

Descripiton:

Power roof exhausters for 3" or 4" roof shall have a 12" diameter throat, capable of 280 CFM air movement at 1/8" static pressure and shall be equipped with adjustable thermostats. Power requirements of exhauster shall be .86 amps at 115 volts.

An intake louver of 115 square inches minimum free air area should be provided for each exhauster.


Name:

Roof Curbs

Descripiton:

Roof curbs shall be constructed of nominal 18 gauge galvalume 14 gauge galvanized steel framing members. Minimum height of curb shall be 8". All flashings shall be provided to ensure water tightness. Optional hatch or cover is available. Note: Interior clear height may be affected.


Name:

Skylights

Descripiton:

Skylight panels shall be flat polycarbonate sheet, factory assembled into standard 16" wide flush interlocking panel. The polycarbonate sheet shall be 1/8" thick, clear with a matte finish, having a light transmission factor of approximately 70%. The panels shall meet ANSI Z97.1 safety
glazing standard and UL94 flammability rating.

1. Skylight panels must be used alternately with solid panels.


2. Skylight for 6" rib roof panels are 8" wide in lieu of 12".


3. Skylight panels are field located as required.

Panels shall meet or exceed all requirements of Federal Specifications LP-505C. When subjected to ASTM-E-55T (Type U Equipment) simulated 1000 hours weather test, the panel shall show no loss of surface gloss or exposed glass fibers.

 

Specifications for Interior Wall Finishes

Name:

Roll In Insulation

Descripiton:

The building walls shall be insulated with 3" thick, fiberglass faced on its exposed side with a white metalized polypropylene scrimkraft facing. The faced insulation shall have a UL Flame Spread Rating of 25 when tested in accordance with UL723 of ASTM E-84 procedures. The insulation shall be retained between the interlocking panel ribs with a white PVC hat clip over the panel ribs. Hat clips shall be of self extinguishing material per UL Standard 651.

The "U" value through the insulated wall shall be a maximum of 0.19 BTU's per square foot when calculated in accordance with the "Zone Method" contained in ASHRAE "Handbook of Fundamentals", 1981 edition.


Name:

Friction Fit Insulation

Descripiton:

The wall system shall include 3-1/2" thick R13 unfaced fiberglass insulation. The "U" value of the finished wall system shall not exceed 0.16 BTU's per square foot when calculated in accordance with the "Zone Method" contained in ASHRAE "Handbook of Fundamentals", 1981 edition.

Interior finish and vapor barrier for the wall system shall be supplied by others.


Name:

Lock-In Wall Liner

Descripiton:

The interior of the building shall be lined with a factory assembled insulated metal liner having no exposed fasteners except at the matching base, ceiling and accessory trim.

Liner panels shall be 16" wide and shall be nominal 26 gauge embossed galvanized steel, prepainted Arctic White. Insulation shall be non combustible, nominal 1" thick, 2# density fiberglass laminated to the liner panel. The "U" value of the finished wall system shall not exceed 0.19 BTU/sf when measured in accordance with ASTMC-236.

Options: The void between the exterior wall panel and the lock-in liner shall be insulated with 3-1/2" thick R11 unfaced fiberglass insulation. The "U" value...0.13 BTU/sf when measured in accordance with ASTMC-236.

Name:

Lock-In Wall Liner Plus

Descripiton:

The interior of the building shall be lined with a factory assembled insulated metal liner having no exposed fasteners except at the matching base, ceiling and accessory trim.

The wall liner system shall have a concealed insulating board of 1 1/2" thick polyisocyanurate foam impaled on rib clips.

Liner panels shall be 16" wide and shall be nominal 26 gauge embossed galvanized steel, prepainted Arctic White. Insulation shall be non combustible, nominal 1" thick, 2# density fiberglass laminated to the liner panel.

The void between the exterior wall panel and the lock-in liner shall be insulated with 3-1/2" thick R11 unfaced fiberglass insulation with a calculated U of .05 for the total system.


Name:

Formed Wall Liner

Descripiton:

The interior of the metal walls shall be lined with 32" wide, nominal 26 gauge galvanized steel panels, prepainted Arctic White with 1/4" high by 1" wide flutes on 8" centers. The exterior panel void shall have 3-1/2" thick R11 unfaced fiberglass insulation.

The liner system shall be furnished complete with White base molding and White trim.

The "U" value of the finished wall system shall be 0.16 BTU's per square foot when calculated in accordance with the "Zone Method" contained in ASHRAE "Handbook of Fundamentals", 1981 edition.


Name:

A29 Acoustical Wall Liner

Descripiton:

The A29 Acoustical Wall System consists of a nominal 24 gauge galvanized steel panel, prepainted Arctic White with 1/4" high by 1" wide flutes on 8" centers. The liner panel shall have 1/8" diameter perforations spaced on 3/8" staggered centers. The exterior panel void shall have 3-1/2" thick R11 unfaced fiberglass insulation. There shall be an eight inch thick, one inch wide, closed cell foam tape installed between the interior perforated liner and the exterior wall panel flange. The system shall have a NRC rating of 0.90 and STC rating of 29 when tested in accordance with ASTM E90 and E413.


Name:

A49 Acoustical Wall Liner

Descripiton:

The A49 Acoustical Wall System consists of a nominal 24 gauge fluted exterior panel with a minimum 3" thick, 16" wide, 4# density fibrous acoustical insulation in panel void. A 1/2" thick sound buffer board shall separate the exterior wall system and a flush 26 gauge metal septum
panel. The septum panels shall be installed perpendicular to the exterior wall panels with voids filled with 3" thick, 16" wide, 4# density fibrous acoustical insulation. A vibration retardant tape will be installed between the septum panel ribs and a perforated formed liner panel. The system shall have NRC of 1.00 and STC of 49 when tested in accordance with ASTM E90 and E413.


Name:

Gypsum Board

Descripiton:

The wall system shall include 3 1/2" thick, R11 unfaced fiberglass batt insulation, vapor barrier (optional), furring strips and 1/2" thick gypsum board.


Name:

Perforated Formed Wall Liner

Descripiton:

The liner shall have 1/8" diameter perforations spaced on 3/8" staggered centers. The complete wall system shall have been certified by an independent testing laboratory to have a minimum NRC rating of 0.90 when tested in accordance with ASTM C423 standards.


Name:

Partitions

Descripiton:

Partitions shall be constructed of 3" x 16" interlocking flush type smooth or embossed surfaced panels in a nominal 24 gauge galvanized steel, factory painted Arctic White. Partitions will be furnished complete with base channel, wall cap and all required fasteners.

Specifications for Interior Roof Finishes

Name:

Partitions

Descripiton:

Partitions shall be constructed of 3" x 16" interlocking flush type smooth or embossed surfaced panels in a nominal 24 gauge galvanized steel, factory painted Arctic White. Partitions will be furnished complete with base channel, wall cap and all required fasteners.


Name:

Ceiling

Descripiton:

The metal ceiling system shall consist of 3" deep 16" wide interlocking panels of nominal 24 gauge embossed galvanized steel, factory painted Arctic White. The ceiling system shall be supported at its perimeter by concealed angles and hook bolts. The ceiling system shall be furnished complete with all necessary connectors and fasteners.

Options:
  • The ceiling shall be insulated with 16" wide by 3-1/2" thick R13 unfaced fiberglass insulation laid at right angles to the panel ribs. The "U" value through the finished ceiling shall be a maximum of 0.09 BTU's per square foot when calculated in accordance with the "Zone Method" contained in ASHRAE "Handbook of Fundamentals", 1981 edition. Eave height -6".
  • The ceiling shall be insulated with 2 layers of 16" wide by 3-1/2" thick R13 unfaced fiberglass insulation 1st layer laid in panel void, 2nd laid at right angles to the panel ribs. The "U" value through the finished ceiling shall be a maximum of 0.06 BTU's per square foot (R15.9) when
    calculated in accordance with the "Zone Method" contained in ASHRAE "Handbook of Fundamentals", 1981 edition. Eave height -6".
  • The ceiling shall be insulated with 2 layers of 16" wide by 3 1/2" thick R-13 unfaced fiberglass insulation laid at right angles to the panel fibs. The "U" value through the finished ceiling shall be a maximum of 0.05 BTU's per square foot (R21.3) when calculated in accordance with the "Zone Method" contained in ASHRAE "Handbook of Fundamentals", 1981 edition. Eave height -9".
  • Ceiling panels shall have acoustical perforations across 14" of the panel width. Perforations shall be 1/8" diameter on a patterned spacing of 3/8". The ceiling system shall have been certified by an independent testing laboratory for a minimum NRC rating of 0.95 when tested in accordance with ASTM C423 standards.

Name:

Roof Insulation

Descripiton:

Roof insulation shall consist of 48" wide, 3" thick, .6# density fiberglass faced on its exposed side with a white metalized polyproplene scrimkraft facing. The faced insulation material shall have a UL Flame Spread Rating of 25 when tested in accordance with UL 723 or ASTM E-84 procedures.

Insulation shall be supported at the roof line by means of mechanical clips spaced on maximum 4' centers and shall be
sealed by means of a 2" side tabs on the facing. The "U" value through the insulated roof shall be a maximum of 0.10 BTU's per square foot when calculated in accordance with the "Zone Method" contained in ASHRAE "Handbook of Fundamentals", 1981 edition.


Name:

3" Therma-Roof

Descripiton:

Roof insulation shall consist of 48" wide x 8' and 12' long polyisocyanurate foam board faced with a white embossed coated foil on the exposed interior surface.

Insulation shall have a maximum UL Flame Spread Rating of 25, fuel contributed rating of 10 and Smoke Developed Rating of 155-190 when tested in accordance with UL723 testing methods and shall meet the requirements of the Underwriters Laboratories "Wall-Ceiling" Construction Classification.

The roof insulation system shall include metal supporting tees on 4' centers and all trim required for a finished interior appearance.

Insulation thickness shall be 3", R9.1, R Value shall be calculated by the "Zone" method contained in ASHRAE "Handbook of Fundamentals" 1981 edition.

 