Specifications for Doors
| Name: |
Hollow Metal Doors |
| Descripiton: |
All doors shall be 1-3/4" thick flush type. Door panels
shall be nominal 20 gauge galvanized steel reinforced by
lamination to a honeycomb core enclosed with 16 gauge end
channel. The hinge reinforcements shall be nominal 7 gauge
and the lock reinforcements shall be nominal 16 gauge. Door
frames shall be 4-3/4" deep double rabbeted type of nominal
16 gauge galvanized steel.
Doors and frames shall be factory painted with one coat of
baked on primer. All doors shall be preassembled in their
frames and hardware installed and tested prior to shipment.
Field installation of single leaf door units shall not
require any frame assembly, or door hanging.
|
| Standard: |
- 3 - 4-1/2" x 4-1/2" standard weight, plain bearing hinges
per ANSI A5133 630 Satin Stainless Finish with non- rising
pins.
- 3-11/16" wide x 5/8" high extruded aluminum threshold. (Out
Swing)
- 1/4" x 1/2" silicone rubber weatherstripping.
|
| Options: |
- 3 - 4 1/2" x 4 1/2" standard weight ball bearing hinges per
ANSI A5112 630 Satin Stainless Finish with non-rising pins.
- Mortise lockset per ANSI A156.13, Series 1000, Grade 1,
Function F13, 626 Satin Chrome Finish (levers both sides).
- Cylindrical key in knob lockset per ANSI A156.2, Series
4000, Grade 2, Function F81, 630 Satin Stainless Steel
Finish.
- Passage set per ANSI A156.2, Series 4000, Grade 2, Function
F75, 626 Satin Chrome Finish.
- Door closer is certified to conform to ANSI 156.4 Grade 1
and meets exterior barrier free codes in 689 Aluminum
Lacquer Finish.
- Rim Type "Cross Bar" panic device per ANSI A156.3, Type 1,
Grade 1, Function 05, with 627 Satin Aluminum Finish.
- Rim type "Push Pad" panic device built to ANSI A156.3, Type
1, Grade 2, Function 08 with 689 Aluminum Lacquer Interior
Finish and 626 Satin Chrome Exterior Finish.
- 23" wide X 20" high Adjustable blade louver with mesh insect
screen.
|
Specifications for Framed Openings
| Name: |
Framed Openings for Overhead Doors |
| Descripiton: |
Framed openings shall be constructed from nominal 12 gauge
galvanized steel. The jambs and head shall provide a
minimum 2-1/2" wide inside surface for field mounting of
overhead door track and hardware. Head and jamb covers to
be nominal 24 gauge, embossed, painted wall color.
|
| Standard: |
|
| Options: |
- Sliding doors shall consist of a nominal 16 gauge galvanized
steel channel framing system and embossed nominal 24 gauge
prepainted arctic white ribbed covering. The doors shall be
top hung design with a bottom guide rail.
- Removable wall sections shall consist of a framed opening
capable of supporting roof and wall loads when the wall
section is removed. The removable section shall consist of
the same materials as the permanent wall. Section shall be
removable by unbolting from the inside of the building.
|
Specifications for Windows
| Name: |
Horizontal Sliding Windows |
| Descripiton: |
Sliding windows shall be furnished factory glazed and
complete with all attaching hardware and screen. The window
unit shall be factory assembled for single unit
installation.
All window sash sections shall be of 6063-T5 extruded
aluminum and shall be color finished in white or bronze
baked enamel. Windows shall meet or exceed ANSI/AAMA 101
and AAMA 1302.5 Specifications.
|
| Standard: |
|
| Options: |
- 1/4" polished wire glass.
- 1/4" acrylic glazing.
- 1/4" obscure glass.
- 1/4" polycarbonate glazing.
|
| Name: |
Fixed Window |
| Descripiton: |
Fixed windows shall be furnished factory glazed and complete
with all attaching hardware. The window unit shall be
factory assembled for single unit installation. All window
sash sections shall be formed from nominal 18 gauge
galvanized G90 steel and factory color finished white or
bronze baked on enamel.
|
| Standard: |
|
| Options: |
- 1/4" polished wire glass.
- 1/4" acrylic glazing.
- 1/4" obscure glass.
- 1/4" polycarbonate glazing.
|
Specifications for Wall Opening Kits
| Name: |
Wall Opening Kit |
| Descripiton: |
The building manufacturer shall supply all necessary framing
and connectors to structurally replace the panels removed by
any wall opening. All trim and flashings required to make
weathertight the unit placed in any opening shall be
provided by the supplier of the unit being installed.
|
Specifications for Louvers
| Name: |
Adjustable Wall Louvers |
| Descripiton: |
Adjustable louvers shall be of self framing design. The
louver frame shall be of nominal 14 gauge formed aluminum
and the louver blades shall be nominal 12 gauge extruded
aluminum. Finish shall be natural mill finish and shall not
require field painting.
Blades shall be pivoted on 1/2" diameter aluminum pivot pins
through nylon flanged bearings and operated by means of a
pull bar operating handle. All louvers shall be complete
with an exterior mounted 18 X 14 aluminum mesh insect
screen.
|
| Options: |
- Wall louvers shall have removable filters.
- Motor Operator
- 1/4" obscure glass.
- 1/4" polycarbonate glazing.
|
| Name: |
Fixed Wall Louvers |
| Descripiton: |
Fixed louvers shall be nominal 26 Gauge., G90 Galvanized
Steel, 16"x16", general purpose type of self framing design
with free area of 75 square inches. Finish shall be bright
galvanized All louvers shall be complete with #8 insect
screening.
|
| Name: |
Gable Louvers |
| Descripiton: |
Gable Louvers shall be fixed blade type with blades set on a 45 degree slope. Blades and frames shall be nominal 14 gauge extruded aluminum with natural mill finish. Louvers shall include #18-14 aluminum mesh insect screens.
|
Specifications for Exterior Roof Accessories
| Name: |
Turbine Ventilator |
| Descripiton: |
Turbine vents shall be wind driven rotary type gravity roof
ventilator with 8" or 12" diameter throat, fabricated from
galvanized steel, externally braced.
|
| Name: |
Circular Roof Ventilators |
| Descripiton: |
Stationary ventilators for 3" or 4" roofs shall be 12"
diameter gravity type fabricated from aluminum and shall be
furnished complete with bird screen, operable disc type
damper with chain and base.
|
| Name: |
Power Roof Ventilators |
| Descripiton: |
Power roof exhausters for 3" or 4" roof shall have a 12"
diameter throat, capable of 280 CFM air movement at 1/8"
static pressure and shall be equipped with adjustable
thermostats. Power requirements of exhauster shall be .86
amps at 115 volts.
An intake louver of 115 square inches minimum free air area
should be provided for each exhauster.
|
| Name: |
Roof Curbs |
| Descripiton: |
Roof curbs shall be constructed of nominal 18 gauge
galvalume 14 gauge galvanized steel framing members.
Minimum height of curb shall be 8". All flashings shall be
provided to ensure water tightness. Optional hatch or cover
is available. Note: Interior clear height may be affected.
|
| Name: |
Skylights |
| Descripiton: |
Skylight panels shall be flat polycarbonate sheet, factory
assembled into standard 16" wide flush interlocking panel.
The polycarbonate sheet shall be 1/8" thick, clear with a
matte finish, having a light transmission factor of
approximately 70%. The panels shall meet ANSI Z97.1 safety
glazing standard and UL94 flammability rating.
1. Skylight panels must be used alternately with solid panels.
2. Skylight for 6" rib roof panels are 8" wide in lieu of
12".
3. Skylight panels are field located as required.
Panels shall meet or exceed all requirements of Federal
Specifications LP-505C. When subjected to ASTM-E-55T (Type
U Equipment) simulated 1000 hours weather test, the panel
shall show no loss of surface gloss or exposed glass fibers.
|
Specifications for Interior Wall Finishes
| Name: |
Roll In Insulation |
| Descripiton: |
The building walls shall be insulated with 3" thick, fiberglass faced on its exposed side with a white metalized polypropylene scrimkraft facing. The faced insulation shall have a UL Flame Spread Rating of 25 when tested in accordance with UL723 of ASTM E-84 procedures. The insulation shall be retained between the interlocking panel ribs with a white PVC hat clip over the panel ribs. Hat clips shall be of self extinguishing material per UL Standard 651.
The "U" value through the insulated wall shall be a maximum of 0.19 BTU's per square foot when calculated in accordance with the "Zone Method" contained in ASHRAE "Handbook of Fundamentals", 1981 edition.
|
| Name: |
Friction Fit Insulation |
| Descripiton: |
The wall system shall include 3-1/2" thick R13 unfaced
fiberglass insulation. The "U" value of the finished wall
system shall not exceed 0.16 BTU's per square foot when
calculated in accordance with the "Zone Method" contained in
ASHRAE "Handbook of Fundamentals", 1981 edition.
Interior finish and vapor barrier for the wall system shall
be supplied by others.
|
| Name: |
Lock-In Wall Liner |
| Descripiton: |
The interior of the building shall be lined with a factory
assembled insulated metal liner having no exposed fasteners
except at the matching base, ceiling and accessory trim.
Liner panels shall be 16" wide and shall be nominal 26 gauge
embossed galvanized steel, prepainted Arctic White.
Insulation shall be non combustible, nominal 1" thick, 2#
density fiberglass laminated to the liner panel. The "U"
value of the finished wall system shall not exceed 0.19
BTU/sf when measured in accordance with ASTMC-236.
|
| Options: |
The void between the exterior wall panel and the lock-in
liner shall be insulated with 3-1/2" thick R11 unfaced
fiberglass insulation. The "U" value...0.13 BTU/sf when
measured in accordance with ASTMC-236. |
| Name: |
Lock-In Wall Liner Plus |
| Descripiton: |
The interior of the building shall be lined with a factory
assembled insulated metal liner having no exposed fasteners
except at the matching base, ceiling and accessory trim.
The wall liner system shall have a concealed insulating
board of 1 1/2" thick polyisocyanurate foam impaled on rib
clips.
Liner panels shall be 16" wide and shall be nominal 26 gauge
embossed galvanized steel, prepainted Arctic White.
Insulation shall be non combustible, nominal 1" thick, 2#
density fiberglass laminated to the liner panel.
The void between the exterior wall panel and the lock-in
liner shall be insulated with 3-1/2" thick R11 unfaced
fiberglass insulation with a calculated U of .05 for the
total system.
|
| Name: |
Formed Wall Liner |
| Descripiton: |
The interior of the metal walls shall be lined with 32"
wide, nominal 26 gauge galvanized steel panels, prepainted
Arctic White with 1/4" high by 1" wide flutes on 8" centers.
The exterior panel void shall have 3-1/2" thick R11 unfaced
fiberglass insulation.
The liner system shall be furnished complete with White base
molding and White trim.
The "U" value of the finished wall system shall be 0.16
BTU's per square foot when calculated in accordance with the "Zone Method" contained in ASHRAE "Handbook of
Fundamentals", 1981 edition.
|
| Name: |
A29 Acoustical Wall Liner |
| Descripiton: |
The A29 Acoustical Wall System consists of a nominal 24
gauge galvanized steel panel, prepainted Arctic White with
1/4" high by 1" wide flutes on 8" centers. The liner panel
shall have 1/8" diameter perforations spaced on 3/8"
staggered centers. The exterior panel void shall have
3-1/2" thick R11 unfaced fiberglass insulation. There shall
be an eight inch thick, one inch wide, closed cell foam tape
installed between the interior perforated liner and the
exterior wall panel flange. The system shall have a NRC
rating of 0.90 and STC rating of 29 when tested in
accordance with ASTM E90 and E413.
|
| Name: |
A49 Acoustical Wall Liner |
| Descripiton: |
The A49 Acoustical Wall System consists of a nominal 24
gauge fluted exterior panel with a minimum 3" thick, 16"
wide, 4# density fibrous acoustical insulation in panel
void. A 1/2" thick sound buffer board shall separate the
exterior wall system and a flush 26 gauge metal septum
panel. The septum panels shall be installed perpendicular
to the exterior wall panels with voids filled with 3" thick,
16" wide, 4# density fibrous acoustical insulation. A
vibration retardant tape will be installed between the
septum panel ribs and a perforated formed liner panel. The
system shall have NRC of 1.00 and STC of 49 when tested in
accordance with ASTM E90 and E413.
|
| Name: |
Gypsum Board |
| Descripiton: |
The wall system shall include 3 1/2" thick, R11 unfaced
fiberglass batt insulation, vapor barrier (optional),
furring strips and 1/2" thick gypsum board.
|
| Name: |
Perforated Formed Wall Liner |
| Descripiton: |
The liner shall have 1/8" diameter perforations spaced on
3/8" staggered centers. The complete wall system shall have
been certified by an independent testing laboratory to have
a minimum NRC rating of 0.90 when tested in accordance with
ASTM C423 standards.
|
| Name: |
Partitions |
| Descripiton: |
Partitions shall be constructed of 3" x 16" interlocking
flush type smooth or embossed surfaced panels in a nominal
24 gauge galvanized steel, factory painted Arctic White.
Partitions will be furnished complete with base channel,
wall cap and all required fasteners.
|
Specifications for Interior Roof Finishes
| Name: |
Partitions |
| Descripiton: |
Partitions shall be constructed of 3" x 16" interlocking
flush type smooth or embossed surfaced panels in a nominal
24 gauge galvanized steel, factory painted Arctic White.
Partitions will be furnished complete with base channel,
wall cap and all required fasteners.
|
| Name: |
Ceiling |
| Descripiton: |
The metal ceiling system shall consist of 3" deep 16" wide
interlocking panels of nominal 24 gauge embossed galvanized
steel, factory painted Arctic White. The ceiling system
shall be supported at its perimeter by concealed angles and
hook bolts. The ceiling system shall be furnished complete
with all necessary connectors and fasteners.
|
| Options: |
- The ceiling shall be insulated with 16" wide by 3-1/2" thick
R13 unfaced fiberglass insulation laid at right angles to
the panel ribs. The "U" value through the finished ceiling
shall be a maximum of 0.09 BTU's per square foot when
calculated in accordance with the "Zone Method" contained in
ASHRAE "Handbook of Fundamentals", 1981 edition. Eave
height -6".
- The ceiling shall be insulated with 2 layers of 16" wide by
3-1/2" thick R13 unfaced fiberglass insulation 1st layer
laid in panel void, 2nd laid at right angles to the panel
ribs. The "U" value through the finished ceiling shall be a
maximum of 0.06 BTU's per square foot (R15.9) when
calculated in accordance with the "Zone Method" contained in
ASHRAE "Handbook of Fundamentals", 1981 edition. Eave
height -6".
- The ceiling shall be insulated with 2 layers of 16" wide by
3 1/2" thick R-13 unfaced fiberglass insulation laid at
right angles to the panel fibs. The "U" value through the
finished ceiling shall be a maximum of 0.05 BTU's per square
foot (R21.3) when calculated in accordance with the "Zone
Method" contained in ASHRAE "Handbook of Fundamentals", 1981
edition. Eave height -9".
- Ceiling panels shall have acoustical perforations across 14"
of the panel width. Perforations shall be 1/8" diameter on
a patterned spacing of 3/8". The ceiling system shall have
been certified by an independent testing laboratory for a
minimum NRC rating of 0.95 when tested in accordance with
ASTM C423 standards.
|
| Name: |
Roof Insulation |
| Descripiton: |
Roof insulation shall consist of 48" wide, 3" thick, .6#
density fiberglass faced on its exposed side with a white
metalized polyproplene scrimkraft facing. The faced
insulation material shall have a UL Flame Spread Rating of
25 when tested in accordance with UL 723 or ASTM E-84
procedures.
Insulation shall be supported at the roof line by means of
mechanical clips spaced on maximum 4' centers and shall be
sealed by means of a 2" side tabs on the facing. The "U" value through the insulated roof shall be a maximum
of 0.10 BTU's per square foot when calculated in accordance
with the "Zone Method" contained in ASHRAE "Handbook of
Fundamentals", 1981 edition.
|
| Name: |
3" Therma-Roof |
| Descripiton: |
Roof insulation shall consist of 48" wide x 8' and 12' long
polyisocyanurate foam board faced with a white embossed
coated foil on the exposed interior surface.
Insulation shall have a maximum UL Flame Spread Rating of
25, fuel contributed rating of 10 and Smoke Developed Rating
of 155-190 when tested in accordance with UL723 testing
methods and shall meet the requirements of the Underwriters
Laboratories "Wall-Ceiling" Construction Classification.
The roof insulation system shall include metal supporting
tees on 4' centers and all trim required for a finished
interior appearance.
Insulation thickness shall be 3", R9.1, R Value shall be
calculated by the "Zone" method contained in ASHRAE "Handbook of Fundamentals" 1981 edition.
|
|